# you can disable an alarm notification by setting the 'to' line to: silent template: apcupsd_10min_ups_load on: apcupsd.load class: Utilization type: Power Supply component: UPS os: * hosts: * lookup: average -10m unaligned of percentage units: % every: 1m warn: $this > (($status >= $WARNING) ? (70) : (80)) delay: down 10m multiplier 1.5 max 1h summary: APC UPS load info: APC UPS average load over the last 10 minutes to: sitemgr # Discussion in https://github.com/netdata/netdata/pull/3928: # Fire the alarm as soon as it's going on battery (99% charge) and clear only when full. template: apcupsd_ups_charge on: apcupsd.charge class: Errors type: Power Supply component: UPS os: * hosts: * lookup: average -60s unaligned of charge units: % every: 60s warn: $this < 100 crit: $this < 40 delay: down 10m multiplier 1.5 max 1h summary: APC UPS battery charge info: APC UPS average battery charge over the last minute to: sitemgr template: apcupsd_last_collected_secs on: apcupsd.load class: Latency type: Power Supply component: UPS device calc: $now - $last_collected_t every: 10s units: seconds ago warn: $this > (($status >= $WARNING) ? ($update_every) : ( 5 * $update_every)) delay: down 5m multiplier 1.5 max 1h summary: APC UPS last collection info: APC UPS number of seconds since the last successful data collection to: sitemgr #Send out a warning when SELFTEST code is BT or NG. Code descriptions can be found at: #http://www.apcupsd.org/manual/#:~:text=or%20N/A.-,SELFTEST,-The%20results%20of template: apcupsd_selftest_warning on: apcupsd.selftest lookup: max -1s unaligned match-names of BT,NG units: status every: 10s warn: $this == 1 delay: up 0 down 15m multiplier 1.5 max 1h info: APC UPS self-test failed due to insufficient battery capacity or due to overload. to: sitemgr #Send out a warning when STATUS code is ONBATT,OVERLOAD,LOWBATT,REPLACEBATT,NOBATT,COMMLOST #https://man.archlinux.org/man/apcaccess.8.en#:~:text=apcupsd%20was%20started-,STATUS,-%3A%20UPS%20status.%20One template: apcupsd_status_onbatt on: apcupsd.status lookup: max -1s unaligned match-names of ONBATT units: status every: 10s warn: $this == 1 delay: up 1m down 15m multiplier 1.5 max 1h info: APC UPS has switched to battery power because the input power has failed to: sitemgr template: apcupsd_status_overload on: apcupsd.status lookup: max -1s unaligned match-names of OVERLOAD units: status every: 10s warn: $this == 1 delay: up 0 down 15m multiplier 1.5 max 1h info: APC UPS is overloaded and cannot supply enough power to the load to: sitemgr template: apcupsd_status_lowbatt on: apcupsd.status lookup: max -1s unaligned match-names of LOWBATT units: status every: 10s warn: $this == 1 delay: up 0 down 15m multiplier 1.5 max 1h info: APC UPS battery is low and needs to be recharged to: sitemgr template: apcupsd_status_replacebatt on: apcupsd.status lookup: max -1s unaligned match-names of REPLACEBATT units: status every: 10s warn: $this == 1 delay: up 0 down 15m multiplier 1.5 max 1h info: APC UPS battery has reached the end of its lifespan and needs to be replaced to: sitemgr template: apcupsd_status_nobatt on: apcupsd.status lookup: max -1s unaligned match-names of NOBATT units: status every: 10s warn: $this == 1 delay: up 0 down 15m multiplier 1.5 max 1h info: APC UPS has no battery to: sitemgr template: apcupsd_status_commlost on: apcupsd.status lookup: max -1s unaligned match-names of COMMLOST units: status every: 10s warn: $this == 1 delay: up 0 down 15m multiplier 1.5 max 1h info: APC UPS communication link is lost to: sitemgr