summaryrefslogtreecommitdiffstats
path: root/health/health.d/apcupsd.conf
diff options
context:
space:
mode:
Diffstat (limited to 'health/health.d/apcupsd.conf')
-rw-r--r--health/health.d/apcupsd.conf125
1 files changed, 0 insertions, 125 deletions
diff --git a/health/health.d/apcupsd.conf b/health/health.d/apcupsd.conf
deleted file mode 100644
index 90a72af1..00000000
--- a/health/health.d/apcupsd.conf
+++ /dev/null
@@ -1,125 +0,0 @@
-# you can disable an alarm notification by setting the 'to' line to: silent
-
- template: apcupsd_10min_ups_load
- on: apcupsd.load
- class: Utilization
- type: Power Supply
-component: UPS
- os: *
- hosts: *
- lookup: average -10m unaligned of percentage
- units: %
- every: 1m
- warn: $this > (($status >= $WARNING) ? (70) : (80))
- delay: down 10m multiplier 1.5 max 1h
- summary: APC UPS load
- info: APC UPS average load over the last 10 minutes
- to: sitemgr
-
-# Discussion in https://github.com/netdata/netdata/pull/3928:
-# Fire the alarm as soon as it's going on battery (99% charge) and clear only when full.
- template: apcupsd_ups_charge
- on: apcupsd.charge
- class: Errors
- type: Power Supply
-component: UPS
- os: *
- hosts: *
- lookup: average -60s unaligned of charge
- units: %
- every: 60s
- warn: $this < 100
- crit: $this < 40
- delay: down 10m multiplier 1.5 max 1h
- summary: APC UPS battery charge
- info: APC UPS average battery charge over the last minute
- to: sitemgr
-
- template: apcupsd_last_collected_secs
- on: apcupsd.load
- class: Latency
- type: Power Supply
-component: UPS device
- calc: $now - $last_collected_t
- every: 10s
- units: seconds ago
- warn: $this > (($status >= $WARNING) ? ($update_every) : ( 5 * $update_every))
- delay: down 5m multiplier 1.5 max 1h
- summary: APC UPS last collection
- info: APC UPS number of seconds since the last successful data collection
- to: sitemgr
-
-#Send out a warning when SELFTEST code is BT or NG. Code descriptions can be found at:
-#http://www.apcupsd.org/manual/#:~:text=or%20N/A.-,SELFTEST,-The%20results%20of
- template: apcupsd_selftest_warning
- on: apcupsd.selftest
- lookup: max -1s unaligned match-names of BT,NG
- units: status
- every: 10s
- warn: $this == 1
- delay: up 0 down 15m multiplier 1.5 max 1h
- info: APC UPS self-test failed due to insufficient battery capacity or due to overload.
- to: sitemgr
-
-#Send out a warning when STATUS code is ONBATT,OVERLOAD,LOWBATT,REPLACEBATT,NOBATT,COMMLOST
-#https://man.archlinux.org/man/apcaccess.8.en#:~:text=apcupsd%20was%20started-,STATUS,-%3A%20UPS%20status.%20One
-
- template: apcupsd_status_onbatt
- on: apcupsd.status
- lookup: max -1s unaligned match-names of ONBATT
- units: status
- every: 10s
- warn: $this == 1
- delay: up 1m down 15m multiplier 1.5 max 1h
- info: APC UPS has switched to battery power because the input power has failed
- to: sitemgr
-
- template: apcupsd_status_overload
- on: apcupsd.status
- lookup: max -1s unaligned match-names of OVERLOAD
- units: status
- every: 10s
- warn: $this == 1
- delay: up 0 down 15m multiplier 1.5 max 1h
- info: APC UPS is overloaded and cannot supply enough power to the load
- to: sitemgr
-
- template: apcupsd_status_lowbatt
- on: apcupsd.status
- lookup: max -1s unaligned match-names of LOWBATT
- units: status
- every: 10s
- warn: $this == 1
- delay: up 0 down 15m multiplier 1.5 max 1h
- info: APC UPS battery is low and needs to be recharged
- to: sitemgr
-
- template: apcupsd_status_replacebatt
- on: apcupsd.status
- lookup: max -1s unaligned match-names of REPLACEBATT
- units: status
- every: 10s
- warn: $this == 1
- delay: up 0 down 15m multiplier 1.5 max 1h
- info: APC UPS battery has reached the end of its lifespan and needs to be replaced
- to: sitemgr
-
- template: apcupsd_status_nobatt
- on: apcupsd.status
- lookup: max -1s unaligned match-names of NOBATT
- units: status
- every: 10s
- warn: $this == 1
- delay: up 0 down 15m multiplier 1.5 max 1h
- info: APC UPS has no battery
- to: sitemgr
-
- template: apcupsd_status_commlost
- on: apcupsd.status
- lookup: max -1s unaligned match-names of COMMLOST
- units: status
- every: 10s
- warn: $this == 1
- delay: up 0 down 15m multiplier 1.5 max 1h
- info: APC UPS communication link is lost
- to: sitemgr