# you can disable an alarm notification by setting the 'to' line to: silent template: upsd_10min_ups_load on: upsd.ups_load class: Utilization type: Power Supply component: UPS os: * hosts: * lookup: average -10m unaligned of load units: % every: 1m warn: $this > (($status >= $WARNING) ? (70) : (80)) crit: $this > (($status == $CRITICAL) ? (85) : (95)) delay: down 10m multiplier 1.5 max 1h summary: UPS ${label:ups_name} load info: UPS ${label:ups_name} average load over the last 10 minutes to: sitemgr template: upsd_ups_battery_charge on: upsd.ups_battery_charge class: Errors type: Power Supply component: UPS os: * hosts: * lookup: average -60s unaligned of charge units: % every: 60s warn: $this < 75 crit: $this < 40 delay: down 10m multiplier 1.5 max 1h summary: UPS ${label:ups_name} battery charge info: UPS ${label:ups_name} average battery charge over the last minute to: sitemgr template: upsd_ups_last_collected_secs on: upsd.ups_load class: Latency type: Power Supply component: UPS device calc: $now - $last_collected_t every: 10s units: seconds ago warn: $this > (($status >= $WARNING) ? ($update_every) : ( 5 * $update_every)) crit: $this > (($status == $CRITICAL) ? ($update_every) : (60 * $update_every)) delay: down 5m multiplier 1.5 max 1h summary: UPS ${label:ups_name} last collected info: UPS ${label:ups_name} number of seconds since the last successful data collection to: sitemgr