blob: 12384fac697ef3c3a246ea1ed9b53b1733411a31 (
plain)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
|
# you can disable an alarm notification by setting the 'to' line to: silent
template: apcupsd_10min_ups_load
on: apcupsd.load
os: *
hosts: *
lookup: average -10m unaligned of percentage
units: %
every: 1m
warn: $this > (($status >= $WARNING) ? (70) : (80))
crit: $this > (($status == $CRITICAL) ? (85) : (95))
delay: down 10m multiplier 1.5 max 1h
info: average UPS load over the last 10 minutes
to: sitemgr
# Discussion in https://github.com/netdata/netdata/pull/3928:
# Fire the alarm as soon as it's going on battery (99% charge) and clear only when full.
template: apcupsd_ups_charge
on: apcupsd.charge
os: *
hosts: *
lookup: average -60s unaligned of charge
units: %
every: 60s
warn: $this < 100
crit: $this < (($status == $CRITICAL) ? (60) : (50))
delay: down 10m multiplier 1.5 max 1h
info: average UPS charge over the last minute
to: sitemgr
template: apcupsd_last_collected_secs
on: apcupsd.load
calc: $now - $last_collected_t
every: 10s
units: seconds ago
warn: $this > (($status >= $WARNING) ? ($update_every) : ( 5 * $update_every))
crit: $this > (($status == $CRITICAL) ? ($update_every) : (60 * $update_every))
delay: down 5m multiplier 1.5 max 1h
info: number of seconds since the last successful data collection
to: sitemgr
|