# you can disable an alarm notification by setting the 'to' line to: silent
template: nut_10min_ups_load
on: nut.load
class: Utilization
type: Power Supply
component: UPS
os: *
hosts: *
lookup: average -10m unaligned of load
units: %
every: 1m
warn: $this > (($status >= $WARNING) ? (70) : (80))
crit: $this > (($status == $CRITICAL) ? (85) : (95))
delay: down 10m multiplier 1.5 max 1h
summary: UPS load
info: UPS average load over the last 10 minutes
to: sitemgr
template: nut_ups_charge
on: nut.charge
class: Errors
type: Power Supply
component: UPS
os: *
hosts: *
lookup: average -60s unaligned of battery_charge
units: %
every: 60s
warn: $this < 75
crit: $this < 40
delay: down 10m multiplier 1.5 max 1h
summary: UPS battery charge
info: UPS average battery charge over the last minute
to: sitemgr
template: nut_last_collected_secs
on: nut.load
class: Latency
type: Power Supply
component: UPS device
calc: $now - $last_collected_t
every: 10s
units: seconds ago
warn: $this > (($status >= $WARNING) ? ($update_every) : ( 5 * $update_every))
crit: $this > (($status == $CRITICAL) ? ($update_every) : (60 * $update_every))
delay: down 5m multiplier 1.5 max 1h
summary: NUT last collected
info: Number of seconds since the last successful data collection
to: sitemgr
|