diff --git a/health/health.d/apcupsd.conf b/health/health.d/apcupsd.conf
index fc8f2cd0f..90a72af19 100644
--- a/health/health.d/apcupsd.conf
+++ b/health/health.d/apcupsd.conf
@@ -48,3 +48,78 @@ component: UPS device
summary: APC UPS last collection
info: APC UPS number of seconds since the last successful data collection
to: sitemgr
+
+#Send out a warning when SELFTEST code is BT or NG. Code descriptions can be found at:
+#http://www.apcupsd.org/manual/#:~:text=or%20N/A.-,SELFTEST,-The%20results%20of
+ template: apcupsd_selftest_warning
+ on: apcupsd.selftest
+ lookup: max -1s unaligned match-names of BT,NG
+ units: status
+ every: 10s
+ warn: $this == 1
+ delay: up 0 down 15m multiplier 1.5 max 1h
+ info: APC UPS self-test failed due to insufficient battery capacity or due to overload.
+ to: sitemgr
+
+#Send out a warning when STATUS code is ONBATT,OVERLOAD,LOWBATT,REPLACEBATT,NOBATT,COMMLOST
+#https://man.archlinux.org/man/apcaccess.8.en#:~:text=apcupsd%20was%20started-,STATUS,-%3A%20UPS%20status.%20One
+
+ template: apcupsd_status_onbatt
+ on: apcupsd.status
+ lookup: max -1s unaligned match-names of ONBATT
+ units: status
+ every: 10s
+ warn: $this == 1
+ delay: up 1m down 15m multiplier 1.5 max 1h
+ info: APC UPS has switched to battery power because the input power has failed
+ to: sitemgr
+
+ template: apcupsd_status_overload
+ on: apcupsd.status
+ lookup: max -1s unaligned match-names of OVERLOAD
+ units: status
+ every: 10s
+ warn: $this == 1
+ delay: up 0 down 15m multiplier 1.5 max 1h
+ info: APC UPS is overloaded and cannot supply enough power to the load
+ to: sitemgr
+
+ template: apcupsd_status_lowbatt
+ on: apcupsd.status
+ lookup: max -1s unaligned match-names of LOWBATT
+ units: status
+ every: 10s
+ warn: $this == 1
+ delay: up 0 down 15m multiplier 1.5 max 1h
+ info: APC UPS battery is low and needs to be recharged
+ to: sitemgr
+
+ template: apcupsd_status_replacebatt
+ on: apcupsd.status
+ lookup: max -1s unaligned match-names of REPLACEBATT
+ units: status
+ every: 10s
+ warn: $this == 1
+ delay: up 0 down 15m multiplier 1.5 max 1h
+ info: APC UPS battery has reached the end of its lifespan and needs to be replaced
+ to: sitemgr
+
+ template: apcupsd_status_nobatt
+ on: apcupsd.status
+ lookup: max -1s unaligned match-names of NOBATT
+ units: status
+ every: 10s
+ warn: $this == 1
+ delay: up 0 down 15m multiplier 1.5 max 1h
+ info: APC UPS has no battery
+ to: sitemgr
+
+ template: apcupsd_status_commlost
+ on: apcupsd.status
+ lookup: max -1s unaligned match-names of COMMLOST
+ units: status
+ every: 10s
+ warn: $this == 1
+ delay: up 0 down 15m multiplier 1.5 max 1h
+ info: APC UPS communication link is lost
+ to: sitemgr