blob: 5fd7aa11261dab8d96a29d5dd3a9d1dcc1cce0d9 (
plain)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
|
# you can disable an alarm notification by setting the 'to' line to: silent
template: apcupsd_10min_ups_load
on: apcupsd.load
class: Utilization
type: Power Supply
component: UPS
lookup: average -10m unaligned of percentage
units: %
every: 1m
warn: $this > (($status >= $WARNING) ? (70) : (80))
delay: down 10m multiplier 1.5 max 1h
summary: APC UPS load
info: APC UPS average load over the last 10 minutes
to: sitemgr
# Discussion in https://github.com/netdata/netdata/pull/3928:
# Fire the alarm as soon as it's going on battery (99% charge) and clear only when full.
template: apcupsd_ups_charge
on: apcupsd.charge
class: Errors
type: Power Supply
component: UPS
lookup: average -60s unaligned of charge
units: %
every: 60s
warn: $this < 100
crit: $this < 40
delay: down 10m multiplier 1.5 max 1h
summary: APC UPS battery charge
info: APC UPS average battery charge over the last minute
to: sitemgr
template: apcupsd_last_collected_secs
on: apcupsd.load
class: Latency
type: Power Supply
component: UPS device
calc: $now - $last_collected_t
every: 10s
units: seconds ago
warn: $this > (($status >= $WARNING) ? ($update_every) : ( 5 * $update_every))
delay: down 5m multiplier 1.5 max 1h
summary: APC UPS last collection
info: APC UPS number of seconds since the last successful data collection
to: sitemgr
#Send out a warning when SELFTEST code is BT or NG. Code descriptions can be found at:
#http://www.apcupsd.org/manual/#:~:text=or%20N/A.-,SELFTEST,-The%20results%20of
template: apcupsd_selftest_warning
on: apcupsd.selftest
lookup: max -1s unaligned match-names of BT,NG
units: status
every: 10s
warn: $this == 1
delay: up 0 down 15m multiplier 1.5 max 1h
info: APC UPS self-test failed due to insufficient battery capacity or due to overload.
to: sitemgr
#Send out a warning when STATUS code is ONBATT,OVERLOAD,LOWBATT,REPLACEBATT,NOBATT,COMMLOST
#https://man.archlinux.org/man/apcaccess.8.en#:~:text=apcupsd%20was%20started-,STATUS,-%3A%20UPS%20status.%20One
template: apcupsd_status_onbatt
on: apcupsd.status
lookup: max -1s unaligned match-names of ONBATT
units: status
every: 10s
warn: $this == 1
delay: up 1m down 15m multiplier 1.5 max 1h
info: APC UPS has switched to battery power because the input power has failed
to: sitemgr
template: apcupsd_status_overload
on: apcupsd.status
lookup: max -1s unaligned match-names of OVERLOAD
units: status
every: 10s
warn: $this == 1
delay: up 0 down 15m multiplier 1.5 max 1h
info: APC UPS is overloaded and cannot supply enough power to the load
to: sitemgr
template: apcupsd_status_lowbatt
on: apcupsd.status
lookup: max -1s unaligned match-names of LOWBATT
units: status
every: 10s
warn: $this == 1
delay: up 0 down 15m multiplier 1.5 max 1h
info: APC UPS battery is low and needs to be recharged
to: sitemgr
template: apcupsd_status_replacebatt
on: apcupsd.status
lookup: max -1s unaligned match-names of REPLACEBATT
units: status
every: 10s
warn: $this == 1
delay: up 0 down 15m multiplier 1.5 max 1h
info: APC UPS battery has reached the end of its lifespan and needs to be replaced
to: sitemgr
template: apcupsd_status_nobatt
on: apcupsd.status
lookup: max -1s unaligned match-names of NOBATT
units: status
every: 10s
warn: $this == 1
delay: up 0 down 15m multiplier 1.5 max 1h
info: APC UPS has no battery
to: sitemgr
template: apcupsd_status_commlost
on: apcupsd.status
lookup: max -1s unaligned match-names of COMMLOST
units: status
every: 10s
warn: $this == 1
delay: up 0 down 15m multiplier 1.5 max 1h
info: APC UPS communication link is lost
to: sitemgr
|